An authentication bypass security issue exists within FactoryTalk View Machine Edition Web Browser ActiveX control. Exploitation of this vulnerability allows unauthorized access to the PanelView Plus 7 Series B, including access to the file system, retrieval of diagnostic information, event logs, and more.
A path traversal security issue exists within FactoryTalk View Machine Edition, allowing unauthenticated attackers on the same network as the device to delete any file within the panels operating system. Exploitation of this vulnerability is dependent on the knowledge of filenames to be deleted.
CVE-2024-45824 IMPACT
A remote
code vulnerability exists in the affected products. The vulnerability occurs
when chained with Path Traversal, Command Injection, and XSS Vulnerabilities
and allows for full unauthenticated remote code execution. The link in the
mitigations section below contains patches to fix this issue.
CVE-2024-7513 IMPACT
A code execution vulnerability exists in the affected product. The vulnerability occurs due to improper default file permissions allowing any user to edit or replace files, which are executed by account with elevated permissions.
A privilege escalation vulnerability exists in the affected product. The vulnerability allows low-privilege users to edit scripts, bypassing Access Control Lists, and potentially gaining further access within the system.
A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.
A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE v12. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. This action is allowed without proper authentication verification.
A vulnerability exists in the affected product that allows a malicious user to restart the Rockwell Automation PanelView™ Plus 7 terminal remotely without security protections. If the vulnerability is exploited, it could lead to the loss of view or control of the PanelView™ product.
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
All versions of FactoryTalk View SE disclose the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.