The Telnet service of the SIMATIC HMI Comfort Panels system component in affected products does not require authentication, which may allow a remote attacker to gain access to the device if the service is enabled. Telnet is disabled by default on the SINAMICS Medium Voltage Products (SINAMICS SL150: All versions, SINAMICS SM150: All versions, SINAMICS SM150i: All versions).
SINAMICS medium voltage routable products are affected by a vulnerability in the Sm@rtServer component for remote access that could allow an unauthenticated attacker to cause a denial-of-service condition, and/or execution of limited configuration modifications and/or execution of limited control commands on the SINAMICS Medium Voltage Products, Remote Access (SINAMICS SL150: All versions, SINAMICS SM150: All versions, SINAMICS SM150i: All versions).
The webserver of the affected devices contains a vulnerability that may lead to
a denial of service condition. An attacker may cause a denial of service
situation which leads to a restart of the webserver of the affected device.
The security vulnerability could be exploited by an attacker with network
access to the affected systems. Successful exploitation requires no system
privileges and no user interaction. An attacker could use the vulnerability
to compromise availability of the device.
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.