Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit
internal resource allocation when multiple legitimate diagnostic package
requests are sent to the DCE-RPC interface.
This could lead to a denial of service condition due to lack of memory
for devices that include a vulnerable version of the stack.
The security vulnerability could be exploited by an attacker with network
access to an affected device. Successful exploitation requires no system
privileges and no user interaction. An attacker could use the vulnerability
to compromise the availability of the device.
A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server at port 80/TCP or port 443/TCP of the affected devices could allow remote attackers to perform actions with the permissions of an authenticated user, provided the targeted user has an active session and is induced to trigger the malicious request.
A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server delivers cookies without the "secure" flag. Modern browsers interpreting the flag would mitigate potential data leakage in case of clear text transmission.
A vulnerability has been identified in SIMATIC NET CP 342-5 (incl. SIPLUS variants) (All versions), SIMATIC NET CP 343-1 Advanced (incl. SIPLUS variants) (All versions < V3.0.44), SIMATIC NET CP 343-1 Lean (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 343-1 Standard (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 443-1 Advanced (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-1 Standard (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-5 Basic (incl. SIPLUS variants) (All versions), SIMATIC NET CP 443-5 Extended (All versions), TIM 3V-IE / TIM 3V-IE Advanced (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 3V-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0), TIM 4R-IE (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 4R-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0). The implemented access protection level enforcement of the affected communication processors (CP) could possibly allow unauthenticated users to perform administrative operations on the CPs if network access (port 102/TCP) is available and the CPs' configuration was stored on their corresponding CPUs.