A vulnerability has been identified in SIMATIC CP 343-1 (6GK7343-1EX30-0XE0) (All versions), SIMATIC CP 343-1 Lean (6GK7343-1CX10-0XE0) (All versions), SIPLUS NET CP 343-1 (6AG1343-1EX30-7XE0) (All versions), SIPLUS NET CP 343-1 Lean (6AG1343-1CX10-2XE0) (All versions). Affected products incorrectly validate TCP sequence numbers. This could allow an unauthenticated remote attacker to create a denial of service condition by injecting spoofed TCP RST packets.
Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit
internal resource allocation when multiple legitimate diagnostic package
requests are sent to the DCE-RPC interface.
This could lead to a denial of service condition due to lack of memory
for devices that include a vulnerable version of the stack.
The security vulnerability could be exploited by an attacker with network
access to an affected device. Successful exploitation requires no system
privileges and no user interaction. An attacker could use the vulnerability
to compromise the availability of the device.
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected.
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.