Vulnerabilities
Vulnerable Software
Schneider-Electric:  >> Saitel Dp  Security Vulnerabilities
CWE-522 Insufficiently Protected Credentials vulnerability that could cause unauthorized access and exposure of sensitive information when unauthenticated attacker accesses credentials stored within firmware or system files. With this credential an attacker could subsequently compromise the device if they have physical access to the device.
CVSS Score
8.7
EPSS Score
0.002
Published
2026-06-25
CWE-732 Incorrect Permission Assignment for Critical Resource vulnerability that could cause unauthorized disclosure of password hashes and potential account compromise when an attacker with privileged local access reads improperly protected system files.
CVSS Score
6.7
EPSS Score
0.001
Published
2026-06-25
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.
CVSS Score
9.1
EPSS Score
0.062
Published
2022-03-18
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.
CVSS Score
7.5
EPSS Score
0.017
Published
2022-03-18
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.
CVSS Score
5.3
EPSS Score
0.011
Published
2022-03-18
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems.
CVSS Score
6.7
EPSS Score
0.004
Published
2022-03-18
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure.
CVSS Score
7.8
EPSS Score
0.004
Published
2022-03-18