Vulnerabilities
Vulnerable Software
Yokogawa:  >> Centum Vp  Security Vulnerabilities
CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is installed tampers the password file stored in the computer, the user privilege which CENTUM managed may be escalated. As a result, the control system may be operated with the escalated user privilege. To exploit this vulnerability, the following prerequisites must be met: (1)An attacker has obtained user credentials where the affected product is installed, (2)CENTUM Authentication Mode is used for user authentication when CENTUM VP is used. The affected products and versions are as follows: CENTUM CS 1000, CENTUM CS 3000 (Including CENTUM CS 3000 Entry Class) R2.01.00 to R3.09.50, CENTUM VP (Including CENTUM VP Entry Class) R4.01.00 to R4.03.00, R5.01.00 to R5.04.20, and R6.01.00 and later, B/M9000 CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R7.04.51 and R8.01.01 and later
CVSS Score
7.8
EPSS Score
0.0
Published
2023-04-11
Violation of secure design principles exists in the communication of CAMS for HIS. Affected products and versions are CENTUM series where LHS4800 is installed (CENTUM CS 3000 and CENTUM CS 3000 Small R3.08.10 to R3.09.00), CENTUM series where CAMS function is used (CENTUM VP, CENTUM VP Small, and CENTUM VP Basic R4.01.00 to R4.03.00), CENTUM series regardless of the use of CAMS function (CENTUM VP, CENTUM VP Small, and CENTUM VP Basic R5.01.00 to R5.04.20 and R6.01.00 to R6.09.00), Exaopc R3.72.00 to R3.80.00 (only if NTPF100-S6 'For CENTUM VP Support CAMS for HIS' is installed), B/M9000 CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R8.03.01). If an adjacent attacker successfully compromises a computer using CAMS for HIS software, they can use credentials from the compromised machine to access data from another machine using CAMS for HIS software. This can lead to a disabling of CAMS for HIS software functions on any affected machines, or information disclosure/alteration.
CVSS Score
8.8
EPSS Score
0.002
Published
2022-06-28
Improper authentication vulnerability in the communication protocol provided by AD (Automation Design) server of CENTUM VP R6.01.10 to R6.09.00, CENTUM VP Small R6.01.10 to R6.09.00, CENTUM VP Basic R6.01.10 to R6.09.00, and B/M9000 VP R8.01.01 to R8.03.01 allows an attacker to use the functions provided by AD server. This may lead to leakage or tampering of data managed by AD server.
CVSS Score
9.1
EPSS Score
0.003
Published
2022-04-15
OS command injection vulnerability exists in CENTUM VP R4.01.00 to R4.03.00, CENTUM VP Small R4.01.00 to R4.03.00, CENTUM VP Basic R4.01.00 to R4.03.00, and B/M9000 VP R6.01.01 to R6.03.02, which may allow an attacker who can access the computer where the affected product is installed to execute an arbitrary OS command by altering a file generated using Graphic Builder.
CVSS Score
7.8
EPSS Score
0.005
Published
2022-04-15
There is a path traversal vulnerability in CAMS for HIS Log Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, andfrom R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
CVSS Score
8.1
EPSS Score
0.005
Published
2022-03-11
The following Yokogawa Electric products do not change the passwords of the internal Windows accounts from the initial configuration: CENTUM VP versions from R5.01.00 to R5.04.20 and versions from R6.01.00 to R6.08.0, Exaopc versions from R3.72.00 to R3.79.00.
CVSS Score
9.8
EPSS Score
0.004
Published
2022-03-11
Path traversal vulnerability exists in CAMS for HIS Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
CVSS Score
8.8
EPSS Score
0.007
Published
2022-03-11
'Long-term Data Archive Package' service implemented in the following Yokogawa Electric products creates some named pipe with imporper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
CVSS Score
7.8
EPSS Score
0.0
Published
2022-03-11
CAMS for HIS Log Server contained in the following Yokogawa Electric products is vulnerable to uncontrolled resource consumption. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
CVSS Score
8.1
EPSS Score
0.004
Published
2022-03-11
'Root Service' service implemented in the following Yokogawa Electric products creates some named pipe with improper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
CVSS Score
7.8
EPSS Score
0.0
Published
2022-03-11