Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a malformed packet.
Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a specifically crafted packet to the CODESYS V2 runtime.
Missing Release of Resource after Effective Lifetime vulnerability in OpenSSL implementation of WAGO 750-831/xxx-xxx, 750-880/xxx-xxx, 750-881, 750-889 in versions FW4 up to FW15 allows an unauthenticated attacker to cause DoS on the device.
On WAGO PFC200 devices in different firmware versions with special crafted packets an attacker with network access to the device could cause a denial of service for the login service of the runtime.
On WAGO PFC200 devices in different firmware versions with special crafted packets an authorised attacker with network access to the device can access the file system with higher privileges.
Improper Authentication vulnerability in WAGO 750-8XX series with FW version <= FW07 allows an attacker to change some special parameters without authentication. This issue affects: WAGO 750-852, WAGO 750-880/xxx-xxx, WAGO 750-881, WAGO 750-831/xxx-xxx, WAGO 750-882, WAGO 750-885/xxx-xxx, WAGO 750-889 in versions FW07 and below.
The Web-GUI on WAGO Series 750-88x (750-330, 750-352, 750-829, 750-831, 750-852, 750-880, 750-881, 750-882, 750-884, 750-885, 750-889) and Series 750-87x (750-830, 750-849, 750-871, 750-872, 750-873) devices has undocumented service access.
Wago 750 Series PLCs with firmware version 10 and prior include a remote attack may take advantage of an improper implementation of the 3 way handshake during a TCP connection affecting the communications with commission and service tools. Specially crafted packets may also be sent to Port 2455/TCP/IP, used in Codesys management software, which may result in a denial-of-service condition of communications with commissioning and service tools.