Vulnerabilities
Vulnerable Software
An authorization bypass vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to get a full access to device, bypassing the authorization system.
CVSS Score
9.8
EPSS Score
0.024
Published
2018-04-18
An information disclosure vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to obtain sensitive device information if network access was obtained.
CVSS Score
5.3
EPSS Score
0.002
Published
2018-04-18
An improper authorization vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to change UPS control and shutdown parameters or other critical settings without authorization.
CVSS Score
9.1
EPSS Score
0.004
Published
2018-04-18
A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page "Access Control" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext
CVSS Score
9.8
EPSS Score
0.002
Published
2018-04-18


Contact Us