Ge:  Security Vulnerabilities
GE Digital APM Classic, Versions 4.4 and prior. An insecure direct object reference (IDOR) vulnerability allows user account data to be downloaded in JavaScript object notation (JSON) format by users who should not have access to such functionality. An attacker can download sensitive data related to user accounts without having the proper privileges.
CVSS Score
5.3
EPSS Score
0.002
Published
2020-09-23
GE Digital APM Classic, Versions 4.4 and prior. Salt is not used for hash calculation of passwords, making it possible to decrypt passwords. This design flaw, along with the IDOR vulnerability, puts the entire platform at high risk because an authenticated user can retrieve all user account data and then retrieve the actual passwords.
CVSS Score
7.2
EPSS Score
0.002
Published
2020-09-23
GE Grid Solutions Reason RT Clocks, RT430, RT431, and RT434, all firmware versions prior to 08A05. The device’s vulnerability in the web application could allow multiple unauthenticated attacks that could cause serious impact. The vulnerability may allow an unauthenticated attacker to execute arbitrary commands and send a request to a specific URL that could cause the device to become unresponsive. The unauthenticated attacker may change the password of the 'configuration' user account, allowing the attacker to modify the configuration of the device via the web interface using the new password. This vulnerability may also allow an unauthenticated attacker to bypass the authentication required to configure the device and reboot the system.
CVSS Score
9.8
EPSS Score
0.007
Published
2020-06-02
A local privilege escalation vulnerability has been identified in the GE Digital CIMPLICITY HMI/SCADA product v10.0 and prior. If exploited, this vulnerability could allow an adversary to modify the system, leading to the arbitrary execution of code. This vulnerability is only exploitable if an attacker has access to an authenticated session. GE Digital CIMPLICITY v11.0, released January 2020, contains mitigation for this local privilege escalation vulnerability. GE Digital recommends all users upgrade to GE CIMPLICITY v11.0 or newer.
CVSS Score
6.7
EPSS Score
0.001
Published
2020-04-15
GE Mark VIe Controller has an unsecured Telnet protocol that may allow a user to create an authenticated session using generic default credentials. GE recommends that users disable the Telnet service.
CVSS Score
8.8
EPSS Score
0.002
Published
2020-04-07
GE Mark VIe Controller is shipped with pre-configured hard-coded credentials that may allow root-user access to the controller. A limited application of the affected product may ship without setup and configuration instructions immediately available to the end user. The bulk of controllers go into applications requiring the GE commissioning engineer to change default configurations during the installation process. GE recommends that users reset controller passwords during installation in the operating environment.
CVSS Score
7.8
EPSS Score
0.001
Published
2020-04-07
A restricted desktop environment escape vulnerability exists in the Kiosk Mode functionality of affected devices. Specially crafted inputs can allow the user to escape the restricted environment, resulting in access to the underlying operating system. Affected devices include the following GE Ultrasound Products: Vivid products - all versions; LOGIQ - all versions not including LOGIQ 100 Pro; Voluson - all versions; Versana Essential - all versions; Invenia ABUS Scan station - all versions; Venue - all versions not including Venue 40 R1-3 and Venue 50 R4-5
CVSS Score
6.8
EPSS Score
0.003
Published
2020-02-20
General Electric D20ME devices are not properly configured and reveal plaintext passwords.
CVSS Score
7.5
EPSS Score
0.231
Published
2020-01-23
An issue was found in GE S2020/S2020G Fast Switch 61850, S2020/S2020G Fast Switch 61850 Versions 07A03 and prior. An attacker can inject arbitrary Javascript in a specially crafted HTTP request that may be reflected back in the HTTP response. The device is also vulnerable to a stored cross-site scripting vulnerability that may allow session hijacking, disclosure of sensitive data, cross-site request forgery (CSRF) attacks, and remote code execution.
CVSS Score
5.4
EPSS Score
0.005
Published
2019-12-18
In GE Aestiva and Aespire versions 7100 and 7900, a vulnerability exists where serial devices are connected via an added unsecured terminal server to a TCP/IP network configuration, which could allow an attacker to remotely modify device configuration and silence alarms.