Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules.
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks.
An authorization bypass vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to get a full access to device, bypassing the authorization system.
An information disclosure vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to obtain sensitive device information if network access was obtained.
An improper authorization vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to change UPS control and shutdown parameters or other critical settings without authorization.
A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page "Access Control" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext
A denial of service vulnerability exists in Schneider Electric's MiCOM Px4x (P540 range excluded) with legacy Ethernet board, MiCOM P540D Range with Legacy Ethernet Board, and MiCOM Px4x Rejuvenated could lose network communication in case of TCP/IP open requests on port 20000 (DNP3oE) if an older TCI/IP session is still open with identical IP address and port number.
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied.
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution.