A vulnerability has been identified in SCALANCE LPE9403 (All versions < V2.1). The `i2c` mutex file is created with the permissions bits of `-rw-rw-rw-`. This file is used as a mutex for multiple applications interacting with i2c. This could allow an authenticated attacker with access to the SSH interface on the affected device to interfere with the integrity of the mutex and the data it protects.
A vulnerability has been identified in SCALANCE LPE9403 (All versions < V2.1). A path traversal vulnerability was found in the `deviceinfo` binary via the `mac` parameter. This could allow an authenticated attacker with access to the SSH interface on the affected device to read the contents of any file named `address`.
A vulnerability has been identified in SCALANCE LPE9403 (All versions < V2.1). A heap-based buffer overflow vulnerability was found in the `edgebox_web_app` binary. The binary will crash if supplied with a backup password longer than 255 characters. This could allow an authenticated privileged attacker to cause a denial of service.
A vulnerability has been identified in SIMATIC IPC1047 (All versions), SIMATIC IPC1047E (All versions with maxView Storage Manager < 4.09.00.25611 on Windows), SIMATIC IPC647D (All versions), SIMATIC IPC647E (All versions with maxView Storage Manager < 4.09.00.25611 on Windows), SIMATIC IPC847D (All versions), SIMATIC IPC847E (All versions with maxView Storage Manager < 4.09.00.25611 on Windows). The Adaptec Maxview application on affected devices is using a non-unique TLS certificate across installations to protect the communication from the local browser to the local application.
A local attacker may use this key to decrypt intercepted local traffic between the browser and the application and could perform a man-in-the-middle attack in order to modify data in transit.
A vulnerability has been identified in Totally Integrated Automation Portal (TIA Portal) V15 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions < V16 Update 7), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 6), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 1). Affected products contain a path traversal vulnerability that could allow the creation or overwrite of arbitrary files in the engineering system. If the user is tricked to open a malicious PC system configuration file, an attacker could exploit this vulnerability to achieve arbitrary code execution.
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter “Remote Operation” is enabled. The parameter is disabled by default.
The vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device.
A vulnerability has been identified in Polarion ALM (All versions < V22R2). The application contains a XML External Entity Injection (XXE) vulnerability. This could allow an attacker to view files on the application server filesystem.
A vulnerability has been identified in JT Open (All versions < V11.3.2.0), JT Utilities (All versions < V13.3.0.0). The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted JT files. This could allow an attacker to execute code in the context of the current process.