Delta Electronics DIAEnergie (Version 1.7.5 and prior) is vulnerable to cleartext transmission as the web application runs by default on HTTP. This could allow an attacker to remotely read transmitted information between the client and product.
DIAEnergie Version 1.7.5 and prior is vulnerable to a reflected cross-site scripting attack through error pages that are returned by “.NET Request.QueryString”.
DIAEnergie Version 1.7.5 and prior is vulnerable to stored cross-site scripting when an unauthenticated user injects arbitrary code into the parameter “descr” of the script “DIAE_hierarchyHandler.ashx”.
DIAEnergie Version 1.7.5 and prior is vulnerable to stored cross-site scripting when an unauthenticated user injects arbitrary code into the parameter “name” of the script “DIAE_HandlerAlarmGroup.ashx”.
DIAEnergie Version 1.7.5 and prior is vulnerable to multiple cross-site scripting vulnerabilities when arbitrary code is injected into the parameter “name” of the script “HandlerEnergyType.ashx”.
Delta Electronics DIAEnergie Version 1.7.5 and prior may allow an attacker to add a new administrative user without being authenticated or authorized, which may allow the attacker to log in and use the device with administrative privileges.
A Blind SQL injection vulnerability exists in the /DataHandler/Handler_CFG.ashx endpoint of Delta Electronics DIAEnergie Version 1.7.5 and prior. The application does not properly validate the user-controlled value supplied through the parameter keyword before using it as part of an SQL query. A remote, unauthenticated attacker can exploit this issue to execute arbitrary code in the context of NT SERVICE\MSSQLSERVER.
Delta Electronics DIAEnergie Version 1.7.5 and prior is vulnerable to cross-site request forgery, which may allow an attacker to cause a user to carry out an action unintentionally.