Emerson Rosemount X-STREAM Gas AnalyzerX-STREAM enhanced XEGP, XEGK, XEFD, XEXF – all revisions, The affected products are vulnerable to improper authentication for accessing log and backup data, which could allow an attacker with a specially crafted URL to obtain access to sensitive information.
In Emerson ValveLink v12.0.264 to v13.4.118, a vulnerability in the ValveLink software may allow a local, unprivileged, trusted insider to escalate privileges due to insecure configuration parameters.
A Heap-based Buffer Overflow was found in Emerson OpenEnterprise SCADA Server 2.83 (if Modbus or ROC Interfaces have been installed and are in use) and all versions of OpenEnterprise 3.1 through 3.3.3, where a specially crafted script could execute code on the OpenEnterprise Server.
GE PACSystems RX3i CPE100/115: All versions prior to R9.85,CPE302/305/310/330/400/410: All versions prior to R9.90,CRU/320 All versions(End of Life) may allow an attacker sending specially manipulated packets to cause the module state to change to halt-mode, resulting in a denial-of-service condition. An operator must reboot the CPU module after removing battery or energy pack to recover from halt-mode.
In Emerson Ovation OCR400 Controller 3.3.1 and earlier, a heap-based buffer overflow vulnerability in the embedded third-party FTP server involves improper handling of a long command to the FTP service, which may cause memory corruption that halts the controller or leads to remote code execution and escalation of privileges.
In Emerson Ovation OCR400 Controller 3.3.1 and earlier, a stack-based buffer overflow vulnerability in the embedded third-party FTP server involves improper handling of a long file name from the LIST command to the FTP service, which may cause the service to overwrite buffers, leading to remote code execution and escalation of privileges.
Emerson DeltaV Smart Switch Command Center application, available in versions 11.3.x and 12.3.1, was unable to change the DeltaV Smart Switches’ management password upon commissioning. Emerson released patches for DeltaV workstations to address this issue, and the patches can be downloaded from Emerson’s Guardian Support Portal. Please refer to the DeltaV Security Notification DSN19003 (KBA NK-1900-0808) for more information about this issue. DeltaV versions 13.3 and higher use the Network Device Command Center application to manage DeltaV Smart Switches, and this newer application is not impacted by this issue. After patching the Smart Switch Command Center, users are required to either commission the DeltaV Smart Switches or change password using the tool.
A specially crafted script could bypass the authentication of a maintenance port of Emerson DeltaV DCS Versions 11.3.1, 11.3.2, 12.3.1, 13.3.1, 14.3, R5.1, R6 and prior, which may allow an attacker to cause a denial of service.