A Credentials Management CWE-255 vulnerability exists in the APC UPS Network Management Card 2 AOS v6.5.6, which could cause Remote Monitoring Credentials to be viewed in plaintext when Remote Monitoring is enabled, and then disabled.
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware versions prior to V2.90), Modicon M340 (firmware versions prior to V3.10), Modicon Premium (all versions), Modicon Quantum (all versions), which could cause a possible denial of service when reading invalid data from the controller.
CWE-284: Improper Access Control vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions), which could cause the execution of commands by unauthorized users when using IEC 60870-5-104 protocol.
An Improper Check for Unusual or Exceptional Conditions (CWE-754) vulnerability exists in Modicon Quantum 140 NOE771x1 version 6.9 and earlier, which could cause denial of service when the module receives an IP fragmented packet with a length greater than 65535 bytes. The module then requires a power cycle to recover.
A CWE-119 Buffer Errors vulnerability exists in Modicon M580 CPU - BMEP582040, all versions before V2.90, and Modicon Ethernet Module BMENOC0301, all versions before V2.16, which could cause denial of service on the FTP service of the controller or the Ethernet BMENOC module when it receives a FTP CWD command with a data length greater than 1020 bytes. A power cycle is then needed to reactivate the FTP service.
A Use After Free: CWE-416 vulnerability exists in Zelio Soft 2, V5.2 and earlier, which could cause remote code execution when opening a specially crafted Zelio Soft 2 project file.
A CWE-94: Code Injection vulnerability exists in ProClima (all versions prior to version 8.0.0) which could allow an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
A CWE-119: Buffer Errors vulnerability exists in ProClima (all versions prior to version 8.0.0) which allows an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
A CWE-427: Uncontrolled Search Path Element vulnerability exists in ProClima (all versions prior to version 8.0.0) which could allow a malicious DLL file, with the same name of any resident DLLs inside the software installation, to execute arbitrary code in all versions of ProClima prior to version 8.0.0.
A CWE-787: Out-of-bounds Write vulnerability exists in Interactive Graphical SCADA System (IGSS), Version 14 and prior, which could cause a software crash when data in the mdb database is manipulated.