CWE-284: Improper Access Control vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions), which could cause the execution of commands by unauthorized users when using IEC 60870-5-104 protocol.
An Improper Check for Unusual or Exceptional Conditions (CWE-754) vulnerability exists in Modicon Quantum 140 NOE771x1 version 6.9 and earlier, which could cause denial of service when the module receives an IP fragmented packet with a length greater than 65535 bytes. The module then requires a power cycle to recover.
A CWE-119 Buffer Errors vulnerability exists in Modicon M580 CPU - BMEP582040, all versions before V2.90, and Modicon Ethernet Module BMENOC0301, all versions before V2.16, which could cause denial of service on the FTP service of the controller or the Ethernet BMENOC module when it receives a FTP CWD command with a data length greater than 1020 bytes. A power cycle is then needed to reactivate the FTP service.
A Use After Free: CWE-416 vulnerability exists in Zelio Soft 2, V5.2 and earlier, which could cause remote code execution when opening a specially crafted Zelio Soft 2 project file.
A CWE-94: Code Injection vulnerability exists in ProClima (all versions prior to version 8.0.0) which could allow an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
A CWE-119: Buffer Errors vulnerability exists in ProClima (all versions prior to version 8.0.0) which allows an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
A CWE-427: Uncontrolled Search Path Element vulnerability exists in ProClima (all versions prior to version 8.0.0) which could allow a malicious DLL file, with the same name of any resident DLLs inside the software installation, to execute arbitrary code in all versions of ProClima prior to version 8.0.0.
A CWE-787: Out-of-bounds Write vulnerability exists in Interactive Graphical SCADA System (IGSS), Version 14 and prior, which could cause a software crash when data in the mdb database is manipulated.
In Vijeo Citect 7.30 and 7.40, and CitectSCADA 7.30 and 7.40, a vulnerability has been identified that may allow an authenticated local user access to Citect user credentials.
A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in Triconex TriStation Emulator V1.2.0, which could cause the emulator to crash when sending a specially crafted packet. The emulator is used infrequently for application logic testing. It is susceptible to an attack only while running in off-line mode. This vulnerability does not exist in Triconex hardware products and therefore has no effect on the operating safety functions in a plant.