Vulnerabilities
Vulnerable Software
Remote file inclusion allows an attacker to craft a specific URL referencing the Schneider Electric Modicon BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, or BMXP342030H PLC web server, which, when launched, will result in the browser redirecting to a remote file via a Java script loaded with the web page.
CVSS Score
5.4
EPSS Score
0.003
Published
2019-03-21
Reflected Cross-Site Scripting (nonpersistent) allows an attacker to craft a specific URL, which contains Java script that will be executed on the Schneider Electric Modicon BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, or BMXP342030H PLC client browser.
CVSS Score
5.4
EPSS Score
0.006
Published
2019-03-21
Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules.
CVSS Score
9.8
EPSS Score
0.006
Published
2018-04-18
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks.
CVSS Score
9.8
EPSS Score
0.003
Published
2018-04-18
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied.
CVSS Score
7.5
EPSS Score
0.008
Published
2018-04-18
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization.
CVSS Score
9.8
EPSS Score
0.002
Published
2018-04-18
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution.
CVSS Score
9.8
EPSS Score
0.006
Published
2018-04-18
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow.
CVSS Score
7.5
EPSS Score
0.008
Published
2018-04-18
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.
CVSS Score
7.5
EPSS Score
0.061
Published
2017-06-30
Stack-based buffer overflow in the GoAhead Web Server on Schneider Electric Modicon M340 PLC BMXNOx and BMXPx devices allows remote attackers to execute arbitrary code via a long password in HTTP Basic Authentication data.
CVSS Score
10.0
EPSS Score
0.029
Published
2015-12-21


Contact Us

Shodan ® - All rights reserved