Rockwellautomation:  Security Vulnerabilities
An Information Exposure issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. User credentials are sent to the web server using the HTTP GET method, which may result in the credentials being logged. This could make user credentials available for unauthorized retrieval.
CVSS Score
9.8
EPSS Score
0.035
Published
2017-06-30
A Predictable Value Range from Previous Values issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. Insufficiently random TCP initial sequence numbers are generated, which may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections, resulting in a denial of service for the target device.
CVSS Score
8.6
EPSS Score
0.001
Published
2017-06-30
A "Reusing a Nonce, Key Pair in Encryption" issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. The affected product reuses nonces, which may allow an attacker to capture and replay a valid request until the nonce is changed.
CVSS Score
9.8
EPSS Score
0.0
Published
2017-06-30
A Weak Password Requirements issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. The affected products use a numeric password with a small maximum character size for the password.
CVSS Score
9.8
EPSS Score
0.002
Published
2017-06-30
A Missing Authorization issue was discovered in Rockwell Automation PanelView Plus 6 700-1500 6.00.04, 6.00.05, 6.00.42, 6.00-20140306, 6.10.20121012, 6.10-20140122, 7.00-20121012, 7.00-20130108, 7.00-20130325, 7.00-20130619, 7.00-20140128, 7.00-20140310, 7.00-20140429, 7.00-20140621, 7.00-20140729, 7.00-20141022, 8.00-20140730, and 8.00-20141023. There is no authorization check when connecting to the device, allowing an attacker remote access.
CVSS Score
8.6
EPSS Score
0.126
Published
2017-06-14
A DLL Hijack issue was discovered in Rockwell Automation Connected Components Workbench (CCW). The following versions are affected: Connected Components Workbench - Developer Edition, v9.01.00 and earlier: 9328-CCWDEVENE, 9328-CCWDEVZHE, 9328-CCWDEVFRE, 9328-CCWDEVITE, 9328-CCWDEVDEE, 9328-CCWDEVESE, and 9328-CCWDEVPTE; and Connected Components Workbench - Free Standard Edition (All Supported Languages), v9.01.00 and earlier. Certain DLLs included with versions of CCW software can be potentially hijacked to allow an attacker to gain rights to a victim's affected personal computer. Such access rights can be at the same or potentially higher level of privileges as the compromised user account, including and up to computer administrator privileges.
CVSS Score
7.0
EPSS Score
0.0
Published
2017-05-19
A Resource Exhaustion issue was discovered in Rockwell Automation ControlLogix 5580 controllers V28.011, V28.012, and V28.013; ControlLogix 5580 controllers V29.011; CompactLogix 5380 controllers V28.011; and CompactLogix 5380 controllers V29.011. This vulnerability may allow an attacker to cause a denial of service condition by sending a series of specific CIP-based commands to the controller.
CVSS Score
5.9
EPSS Score
0.0
Published
2017-05-06
An issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 controller 1763-L16AWA, Series A and B, Version 14.000 and prior versions; 1763-L16BBB, Series A and B, Version 14.000 and prior versions; 1763-L16BWA, Series A and B, Version 14.000 and prior versions; and 1763-L16DWD, Series A and B, Version 14.000 and prior versions. User credentials are sent to the web server in clear text, which may allow an attacker to discover the credentials if they are able to observe traffic between the web browser and the server.
CVSS Score
7.3
EPSS Score
0.001
Published
2017-02-13
An issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 controller 1763-L16AWA, Series A and B, Version 14.000 and prior versions; 1763-L16BBB, Series A and B, Version 14.000 and prior versions; 1763-L16BWA, Series A and B, Version 14.000 and prior versions; and 1763-L16DWD, Series A and B, Version 14.000 and prior versions. Because of an Incorrect Permission Assignment for Critical Resource, users with administrator privileges may be able to remove all administrative users requiring a factory reset to restore ancillary web server function. Exploitation of this vulnerability will still allow the affected device to function in its capacity as a controller.
CVSS Score
2.7
EPSS Score
0.0
Published
2017-02-13
An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service.