Vulnerabilities
Vulnerable Software
Rockwellautomation:  Security Vulnerabilities
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. A remote, unauthenticated threat actor may intentionally send specially crafted Ethernet/IP packets to Port 44818, causing the software application to stop responding and crash. The user must restart the software to regain functionality.
CVSS Score
7.5
EPSS Score
0.002
Published
2018-09-20
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. This vulnerability may allow a remote threat actor to intentionally send a malformed CIP packet to Port 44818, causing the software application to stop responding and crash. This vulnerability also has the potential to exploit a buffer overflow condition, which may allow the threat actor to remotely execute arbitrary code.
CVSS Score
9.8
EPSS Score
0.484
Published
2018-09-20
Improperly implemented option-field processing in the TCP/IP stack on Allen-Bradley L30ERMS safety devices v30 and earlier causes a denial of service. When a crafted TCP packet is received, the device reboots immediately.
CVSS Score
7.5
EPSS Score
0.0
Published
2018-06-25
An unquoted search path or element in RSLinx Classic Versions 3.90.01 and prior and FactoryTalk Linx Gateway Versions 3.90.00 and prior may allow an authorized, but non-privileged local user to execute arbitrary code and allow a threat actor to escalate user privileges on the affected workstation.
CVSS Score
7.8
EPSS Score
0.0
Published
2018-06-07
An exploitable file write vulnerability exists in the memory module functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a file write resulting in a new program being written to the memory module. An attacker can send an unauthenticated packet to trigger this vulnerability.
CVSS Score
3.7
EPSS Score
0.001
Published
2018-06-04
Rockwell Automation Arena versions 15.10.00 and prior contains a use after free vulnerability caused by processing specially crafted Arena Simulation Software files that may cause the software application to crash, potentially losing any unsaved data..
CVSS Score
5.5
EPSS Score
0.0
Published
2018-05-14
Without quotation marks, any whitespace in the file path for Rockwell Automation FactoryTalk Activation version 4.00.02 remains ambiguous, which may allow an attacker to link to or run a malicious executable. This may allow an authorized, but not privileged local user to execute arbitrary code with elevated privileges on the system. CVSS v3 base score: 8.8, CVSS vector string: (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H). Rockwell Automation has released a new version of FactoryTalk Activation, Version 4.01, which addresses the identified vulnerability. Rockwell Automation recommends upgrading to the latest version of FactoryTalk Activation, Version 4.01 or later.
CVSS Score
7.8
EPSS Score
0.001
Published
2018-05-11
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC, a fault is triggered. NOTE: This is not possible through RSLogix.
CVSS Score
10.0
EPSS Score
0.426
Published
2018-04-05
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.
CVSS Score
10.0
EPSS Score
0.426
Published
2018-04-05
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Requests a specific set of bytes from an undocumented data file and returns the ASCII version of the master password.
CVSS Score
10.0
EPSS Score
0.426
Published
2018-04-05


Contact Us