Rockwellautomation:  Security Vulnerabilities
All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
CVSS Score
9.0
EPSS Score
0.47
Published
2020-07-20
Rockwell Automation Logix Designer Studio 5000 Versions 32.00, 32.01, and 32.02 vulnerable to an xml external entity (XXE) vulnerability, which may allow an attacker to view hostnames or other resources from the program.
CVSS Score
3.3
EPSS Score
0.015
Published
2020-07-14
In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges.
CVSS Score
8.8
EPSS Score
0.011
Published
2020-06-23
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to specify a filename to execute unauthorized code and modify files or data.
CVSS Score
8.1
EPSS Score
0.028
Published
2020-06-15
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. The parsing mechanism that processes certain file types does not provide input sanitation. This may allow an attacker to use specially crafted files to traverse the file system and modify or expose sensitive data or execute arbitrary code.
CVSS Score
9.8
EPSS Score
0.115
Published
2020-06-15
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to use specially crafted requests to traverse the file system and expose sensitive data on the local hard drive.
CVSS Score
7.5
EPSS Score
0.052
Published
2020-06-15
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. A vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition.
CVSS Score
7.5
EPSS Score
0.018
Published
2020-06-15
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable.The EDS subsystem does not provide adequate input sanitation, which may allow an attacker to craft specialized EDS files to inject SQL queries and manipulate the database storing the EDS files. This can lead to denial-of-service conditions.
CVSS Score
8.2
EPSS Score
0.013
Published
2020-05-20
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable. A memory corruption vulnerability exists in the algorithm that matches square brackets in the EDS subsystem. This may allow an attacker to craft specialized EDS files to crash the EDSParser COM object, leading to denial-of-service conditions.
CVSS Score
5.5
EPSS Score
0.025
Published
2020-05-19
In Rockwell Automation RSLinx Classic versions 4.11.00 and prior, an authenticated local attacker could modify a registry key, which could lead to the execution of malicious code using system privileges when opening RSLinx Classic.