Connected Components Workbench (v13.00.00 and prior), ISaGRAF Workbench (v6.0 though v6.6.9), and Safety Instrumented System Workstation (v1.2 and prior (for Trusted Controllers)) do not limit the objects that can be deserialized. This allows attackers to craft a malicious serialized object that, if opened by a local user in Connected Components Workbench, may result in arbitrary code execution. This vulnerability requires user interaction to be successfully exploited
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
When opening a malicious solution file provided by an attacker, the application suffers from an XML external entity vulnerability due to an unsafe call within a dynamic link library file. An attacker could exploit this to pass data from local files to a remote web server, leading to a loss of confidentiality.
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user.
Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine.
The parsing mechanism that processes certain file types does not provide input sanitization for file paths. This may allow an attacker to craft malicious files that, when opened by Rockwell Automation Connected Components Workbench v12.00.00 and prior, can traverse the file system. If successfully exploited, an attacker could overwrite existing files and create additional files with the same permissions of the Connected Components Workbench software. User interaction is required for this exploit to be successful.
A vulnerability exists in the RunSearch function of SearchService service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier, which may allow for the execution of remote unauthenticated arbitrary SQL statements.
Rockwell Automation Connected Components Workbench v12.00.00 and prior does not sanitize paths specified within the .ccwarc archive file during extraction. This type of vulnerability is also commonly referred to as a Zip Slip. A local, authenticated attacker can create a malicious .ccwarc archive file that, when opened by Connected Components Workbench, will allow the attacker to gain the privileges of the software. If the software is running at SYSTEM level, the attacker will gain admin level privileges. User interaction is required for this exploit to be successful.
Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier does not properly restrict all functions relating to IIS remoting services. This vulnerability may allow a remote, unauthenticated attacker to modify sensitive data in FactoryTalk AssetCentre.
Rockwell Automation Connected Components Workbench v12.00.00 and prior does not limit the objects that can be deserialized. This vulnerability allows attackers to craft a malicious serialized object that, if opened by a local user in Connected Components Workbench, may result in remote code execution. This vulnerability requires user interaction to be successfully exploited.