A vulnerability has been identified in SIPORT MP (All versions < 3.2.1). Vulnerable versions of the device could allow an authenticated attacker to impersonate other users of the system and perform (potentially administrative) actions on behalf of those users if the single sign-on feature ("Allow logon without password") is enabled.
A vulnerability has been identified in Desigo Insight (All versions). The web service does not properly apply input validation for some query parameters in a reserved area. This could allow an authenticated attacker to retrieve data via a content-based blind SQL injection attack.
A vulnerability has been identified in Desigo Insight (All versions). The device does not properly set the X-Frame-Options HTTP Header which makes it vulnerable to Clickjacking attacks. This could allow an unauthenticated attacker to retrieve or modify data in the context of a legitimate user by tricking that user to click on a website controlled by the attacker.
A vulnerability has been identified in Desigo Insight (All versions). Some error messages in the web application show the absolute path to the requested resource. This could allow an authenticated attacker to retrieve additional information about the host system.
A vulnerability has been identified in DCA Vantage Analyzer (All versions < V4.5 are affected by CVE-2020-7590. In addition, serial numbers < 40000 running software V4.4.0 are also affected by CVE-2020-15797). Improper Access Control could allow an unauthenticated attacker to escape from the restricted environment (“kiosk mode”) and access the underlying operating system. Successful exploitation requires direct physical access to the system.
A vulnerability has been identified in DCA Vantage Analyzer (All versions < V4.5 are affected by CVE-2020-7590. In addition, serial numbers < 40000 running software V4.4.0 are also affected by CVE-2020-15797). Affected devices use a hard-coded password to protect the onboard database. This could allow an attacker to read and or modify the onboard database. Successful exploitation requires direct physical access to the device.
A vulnerability has been identified in Polarion Subversion Webclient (All versions). The Polarion subversion web application does not filter user input in a way that prevents Cross-Site Scripting. If a user is enticed into passing specially crafted, malicious input to the web client (e.g. by clicking on a malicious URL with embedded JavaScript), then JavaScript code can be returned and may then be executed by the user’s client. Various actions could be triggered by running malicious JavaScript code.
A vulnerability has been identified in Polarion Subversion Webclient (All versions). The web interface could allow a Cross-Site Request Forgery (CSRF) attack if an unsuspecting user is tricked into accessing a malicious link. Successful exploitation requires user interaction by a legitimate user, who must be authenticated to the web interface. A successful attack could allow an attacker to trigger actions via the web interface that the legitimate user is allowed to perform. This could allow the attacker to read or modify contents of the web application.
A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP8). If configured in an insecure manner, the web server might be susceptible to a directory listing attack.
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 CPU family (incl. SIPLUS variants) (All versions), SIMATIC WinAC RTX (F) 2010 (All versions), SINUMERIK 840D sl (All versions). The authentication protocol between a client and a PLC via port 102/tcp (ISO-TSAP) insufficiently protects the transmitted password. This could allow an attacker that is able to intercept the network traffic to obtain valid PLC credentials.