Abb:  Security Vulnerabilities
The product M2M ETHERNET (FW Versions 2.22 and prior, ETH-FW Versions 1.01 and prior) is vulnerable in that an attacker can upload a malicious language file by bypassing the user authentication mechanism.
CVSS Score
4.3
EPSS Score
0.001
Published
2019-01-31
Pluto Safety PLC Gateway Ethernet devices ABB GATE-E1 and GATE-E2 all versions do not allow authentication to be configured on administrative telnet or web interfaces, which could enable various effects vectors, including conducting device resets, reading or modifying registers, and changing configuration settings such as IP addresses.
CVSS Score
9.8
EPSS Score
0.013
Published
2019-01-03
Pluto Safety PLC Gateway Ethernet devices in ABB GATE-E1 and GATE-E2 all versions allows an unauthenticated attacker using the administrative web interface to insert an HTML/Javascript payload into any of the device properties, which may allow an attacker to display/execute the payload in a visitor browser.
CVSS Score
6.1
EPSS Score
0.003
Published
2019-01-03
ABB Panel Builder 800 all versions has an improper input validation vulnerability which may allow an attacker to insert and run arbitrary code on a computer where the affected product is used.
CVSS Score
7.8
EPSS Score
0.002
Published
2018-07-18
In ABB IP GATEWAY 3.39 and prior, the web server does not sufficiently verify that a request was performed by the authenticated user, which may allow an attacker to launch a request impersonating that user.
CVSS Score
8.8
EPSS Score
0.002
Published
2018-06-06
In ABB IP GATEWAY 3.39 and prior, by accessing a specific uniform resource locator (URL) on the web server, a malicious user is able to access the configuration files and application pages without authentication.
CVSS Score
9.8
EPSS Score
0.023
Published
2018-06-06
In ABB IP GATEWAY 3.39 and prior, some configuration files contain passwords stored in plain-text, which may allow an attacker to gain unauthorized access.
CVSS Score
9.8
EPSS Score
0.004
Published
2018-06-06
In ABB SREA-01 revisions A, B, C: application versions up to 3.31.5, and SREA-50 revision A: application versions up to 3.32.8, an attacker may access internal files of ABB SREA-01 and SREA-50 legacy remote monitoring tools without any authorization over the network using a HTTP request which refers to files using ../../ relative paths. Once the internal password file is retrieved, the password hash can be identified using a brute force attack. There is also an exploit allowing running of commands after authorization.
CVSS Score
9.8
EPSS Score
0.022
Published
2018-05-24
An Information Exposure issue was discovered in ABB netCADOPS Web Application Version 3.4 and prior, netCADOPS Web Application Version 7.1 and prior, netCADOPS Web Application Version 7.2x and prior, netCADOPS Web Application Version 8.0 and prior, and netCADOPS Web Application Version 8.1 and prior. A vulnerability exists in the password entry section of netCADOPS Web Application that may expose critical database information.
CVSS Score
5.8
EPSS Score
0.002
Published
2018-02-20
A Permissions, Privileges, and Access Controls issue was discovered in ABB VSN300 WiFi Logger Card versions 1.8.15 and prior, and VSN300 WiFi Logger Card for React versions 2.1.3 and prior. The web application does not properly restrict privileges of the Guest account. A malicious user may be able to gain access to configuration information that should be restricted.
CVSS Score
6.5
EPSS Score
0.003
Published
2017-08-07