Weak Registry permissions in ABB System 800xA Base allow low privileged users to read and modify registry settings related to control system functionality, allowing an authenticated attacker to cause system functions to stop or malfunction.
The installations for ABB System 800xA Information Manager versions 5.1, 6.0 to 6.0.3.2 and 6.1 wrongly contain an auxiliary component. An attacker is able to use this for an XSS-like attack to an authenticated local user, which might lead to execution of arbitrary code.
The web server in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway allows access to different endpoints of the application without authenticating by accessing a specific uniform resource locator (URL) , violating the access-control (ACL) rules. This issue allows obtaining sensitive information that may aid in further attacks and privilege escalation.
ABB CP651 HMI products revision BSP UN30 v1.76 and prior implement hidden administrative accounts that are used during the provisioning phase of the HMI interface.
Due to a lack of file length check, the HMIStudio component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier crashes when trying to load an empty *.JPR application file. An attacker with access to the file system might be able to cause application malfunction such as denial of service.
The HMISimulator component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier fails to validate the content-length field for HTTP requests, exposing HMISimulator to denial of service via crafted HTTP requests manipulating the content-length setting.
Path settings in HMIStudio component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier accept DLLs outside of the program directory, potentially allowing an attacker with access to the local file system the execution of code in the application’s context.
The HMISimulator component of ABB PB610 Panel Builder 600 uses the readFile/writeFile interface to manipulate the work file. Path configuration in PB610 HMISimulator versions 2.8.0.424 and earlier potentially allows access to files outside of the working directory, thus potentially supporting unauthorized file access.
In all versions of ABB Power Generation Information Manager (PGIM) and Plant Connect, the affected product is vulnerable to authentication bypass, which may allow an attacker to remotely bypass authentication and extract credentials from the affected device.
The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are the idal123 password for the IdalMaster account, and the exor password for the exor account. These credentials are used over both HTTP(S) and FTP. There is no option to disable or change these undocumented credentials. An attacker can use these credentials to login to ABB HMI to read/write HMI configuration files and also to reset the device. This affects ABB CP635 HMI, CP600 HMIClient, Panel Builder 600, IDAL FTP server, IDAL HTTP server, and multiple other HMI components.