Vulnerability Details CVE-2023-39464
Triangle MicroWorks SCADA Data Gateway GTWWebMonitorService Unquoted Search Path Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.
The specific flaw exists within the configuration of the GTWWebMonitorService service. The path to the service executable contains spaces not surrounded by quotations. An attacker can leverage this vulnerability to execute arbitrary code in the context of root. Was ZDI-CAN-20538.
Exploit prediction scoring system (EPSS) score
EPSS Score 0.002
EPSS Ranking 38.8%
CVSS Severity
CVSS v3 Score 7.2
Products affected by CVE-2023-39464
-
cpe:2.3:a:trianglemicroworks:scada_data_gateway:5.1.3.20324