Vulnerabilities
Vulnerable Software

Vulnerability Details CVE-2022-31204

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.
Exploit prediction scoring system (EPSS) score
EPSS Score 0.001
EPSS Ranking 29.4%
CVSS Severity
CVSS v3 Score 7.5
Products affected by CVE-2022-31204


Contact Us

Shodan ® - All rights reserved