Vulnerability Details CVE-2022-2502
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Exploit prediction scoring system (EPSS) score
EPSS Score 0.001
EPSS Ranking 18.4%
CVSS Severity
CVSS v3 Score 7.5
Products affected by CVE-2022-2502
-
cpe:2.3:h:hitachienergy:rtu500:-
-
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.1
-
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.2
-
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.3
-
cpe:2.3:o:hitachienergy:rtu500_firmware:13.4.1